SECTION 9 - SERVICE AND TROUBLESHOOTING
Soft start, Refrigerant Type, and Ex-
pansion Valve Type MUST be properly
programmed or damage to compres-
sors and other system components
may result.
Following is a list, in order of appearance:
DATA LOGGING MODE = : DO NOT MODIFY
DATA LOGGING TIMER = : DO NOT MODIFY
SOFT START
REFRIGERANT TYPE
EXPANSION VALVE TYPE
SYS 1 HOURS
SYS 2 HOURS
SYS 1 STARTS
SYS 2 STARTS
The last displays shown on the above list is for the ac-
cumulated run and start timers for each system. All val-
ues can also be changed using the (UP) and (Down)
arrow keys, but under normal circumstances would not
be advised. After the last start display, the microproces-
sor will display the rst programmable value under the
PROGRAM key.
SERVICE MODE – INPUTS
After entering Service Mode (PROGRAM ↑↑ ↓↓),
all digital and analog inputs to the microboard can
be viewed by pressing the OPER DATA key. After
pressing the OPER DATA key, the (UP) arrow and
(DOWN) arrow keys are used to scroll through the
analog and digital inputs.
Following is the order of analog and digital inputs that
will appear when sequenced with the (Down) arrow
key:
(analog inputs)
SYS 1 *SUCT PRESSURE
UNIT TYPE
SYS 1 **DISCH PRESSURE
SYS 1*** COOLER INLET REFRIG. TEMP.
SYS 2*** COOLER INLET REFRIG. TEMP.
SYS 1**** SUCTION TEMP.
SYS 2**** SUCTION TEMP.
AMBIENT AIR TEMP.
LEAVING LIQUID TEMP.
RETURN LIQUID TEMP.
SYS 2 *SUCTION PRESSURE
SYS 2 SPARE
SYS 2 **DISCH PRESSURE
SYS 1 MTR VOLTS
SYS 2 MTR VOLTS
(digital inputs)
PWM TEMP RESET INPUT
LOAD LIMIT INPUT
FLOW SW / REM START
SPARE
SINGLE SYSTEM SELECT
SYS 1 MP / HPCO INPUT
SYS 2 MP / HPCO INPUT
* The suction pressure transducer is optional on YCAL0041 -
YCAL0071. A low pressure switch is standard on these models in
place of the suction transducer.
** The discharge pressure transducer is optional on some models.
*** The cooler inlet refrigerant temp. sensor is on R-407c units only.
****The suction temp. sensor is on EEV units only.
The analog inputs will display the input connection,
the temperature or pressure, and corresponding input
voltage such as:
S Y S 1 S U C T P R J 7 1 0
2 . 1 V D C = 8 1 P S I G
This example indicates that the system 1 suction pres-
sure input is connected to plug 7 - pin 10 (J7-10) on the
microboard. It indicates that the voltage is 2.1 volts dc
which corresponds to 81 psig (5.6 bars) suction pres-
sure.
The digital inputs will display the input connection and
ON/OFF status such as:
F L O W S W / R E M S T A R T
J 13 5 I S O N
This indicates that the ow switch/remote start input is
connected to plug 13- pin 5 (J13-5) on the microboard,
and is ON (ON = +30VDC unregulated input, OFF =
0VDC input on digital inputs).