SECTION 6 - TECHNICAL DATA
VIEW B-B
3 15/16"
3 1/4"
6 3/4"
BOTTOM OF PANEL
7/8" TYP.
47 3/4"
46 15/16"
45 1/8"
12 5/8"
3" VICTAULIC (typ)
90 1/4" BASE WIDTH
LEFT END
LIQUID OUT
34 5/8"
15 3/4"
9 15/16"
ELECTRICAL ACCESS
PANEL
LIQUID IN
LD10965
DIMENSIONS - YCAL0051 (ENGLISH)
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 6';
rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'. No
more than one adjacent wall may be higher than the unit. 1" nominal deection isolators (not shown) will increase overall unit height by 6".
ALUMINUM COPPER
YCAL
CENTER OF GRAVITY (IN.)
YCAL
CENTER OF GRAVITY (IN.)
X Y X Y
0051 59.2 42.6 0051 64.3 42.9