SECTION 3 - DISPLAY MESSAGES
SAFETY SHUTDOWN MESSAGES
EVAPORATOR – LOW PRESSURE
(This message is applicable only if the Smart Freeze 
feature is not activated. If Smart Freeze is activated and 
has initiated the shutdown, “Evaporator - Low Pressure 
- Smart Freeze” is displayed. Its description follows). 
The evaporator pressure, as sensed by the Evapora-
tor Transducer, has decreased to the safety shutdown 
threshold. For water cooling applications, the safety 
shutdown threshold is a fixed value for the respective 
refrigerant. For Brine cooling applications, the safety 
shutdown threshold varies according to the concentra-
tion of the Brine solution. The Brine shutdown thresh-
old is programmed at the Johnson Controls. It should 
not be changed by anyone other than a qualified Service 
Technician following instructions in OptiView Control 
Center Service Instructions (Form 160.81-M1). The 
chiller can be started after the evaporator pressure in-
creases to the restart threshold and the COMPRESSOR 
switch is placed in the Stop-Reset (O) position.
SHUTDOWN 
(PSIG)
RESTART (PSIG)
Water cooling 
-R134a
25.0 25.1
Brine cooling - 
R134a
6.0 to 25.0 as 
programmed
+0.1 more 
than shutdown 
threshold
EVAPORATOR – LOW PRESSURE - SMART 
FREEZE
(Not applicable to Software version C.MLM.05.04.
xxx (and later). 
Smart Freeze Protection is activated and has shut down 
the chiller because the evaporator temperature has 
been below the Smart Freeze threshold for greater than 
the allowable number of seconds. If the Evaporator 
Refrigerant Temperature Sensor RT7 is enabled (us-
ing procedure in OptiView Control Center Service In-
structions (Form 160.81-M1), this parameter is used as 
the evaporator refrigerant temperature and the freeze 
threshold is 32.8ºF. If RT7 is not enabled, the evapo-
rator refrigerant temperature used is the Evaporator 
Saturation Temperature, derived from the Evaporator 
Pressure Transducer and the freeze threshold is 34.0°F.
The count is incremented once for every second the 
evaporator refrigerant temperature is below the freeze 
threshold (but is never decremented below zero). The 
number of seconds it will take the chilled liquid to 
freeze is based on how far the evaporator refrigerant 
temperature is below the freeze threshold as follows:
Number of seconds to freezing = (4053.7) / (freeze 
threshold-evaporator refrigerant temperature)
Smart Freeze is activated only if the feature has been 
enabled by a Service Technician (following instruc-
tions in OptiView Control Center Service Instructions 
(Form 160.81-M1) and the Leaving Chilled Liquid 
Temperature setpoint is less than 38.0ºF.
The Smart Freeze feature has been removed from pres-
ent production software. It is no longer available in 
software versions C.MLM.05.04.xxx (and later).    
EVAPORATOR – TRANSDUCER OR LEAVING 
LIQUID PROBE
A possible defective Evaporator Pressure Transducer 
or Leaving Chilled Liquid Temperature Thermistor has 
been detected. The pressure and temperature that these 
devices are indicating are not in the correct relation-
ship to each other. The Control Center converts the 
evaporator pressure to a Saturated Temperature value 
and compares this value to the Leaving Chilled Liquid 
Temperature (difference = chilled liquid temp – evap-
orator saturated temp). The difference should not be 
outside the range of –2.5ºF to +25.0ºF. If the transducer 
and thermistor are accurate, the Evaporator Saturated 
Temperature should not be more than 2.5º warmer or 
more than 25.0ºF colder than the Leaving Chilled Liq-
uid Temperature. In order to initiate a shutdown, the 
difference must be outside the acceptable range contin-
uously for 10 minutes. The chiller can be started after 
the COMPRESSOR switch is placed in the Stop-Reset 
(O) position. This check is not performed when the op-
tional Hot Gas feature is enabled in Brine mode. 
EVAPORATOR – TRANSDUCER OR TEMPERA-
TURE SENSOR
(Not applicable to software version C.MLM.05.04.xxx 
(and later). 
A possible defective Evaporator Pressure Transducer 
or Refrigerant Temperature Sensor has been detected. 
The Control Center converts the evaporator pressure to 
a Saturated Temperature value and compares this value 
to the optional Evaporator Refrigerant Temperature 
Sensor. If the difference between these temperatures is 
greater than 3.0ºF, continuously for 1 minute, this shut-
down is performed. 
This check is only performed under the following con-
ditions: