25
8 Service tasks
Other service are included this items as:
“1.INNER TANK REFILL
2.LANGUAGE SELECT
3.WEIGHT UNIT
4.ZERO BALANCE
5.VACUUM PUMP OIL
6.FILTER DRIVER
7.HOSE COMPENSATION
8.PRESSURE RISE WAIT
9.OTHER SERVICE.”
If you want come to these items , please press key and use
or to select and enter it.
8.1 Inner tank refill
Refer to 6.3
8.2 Language select
You can select Chinese or English according to custom.
8.3 Zero balance
In order to make sure the refrigerant quantities correctly, the zero point of the
scales must be checked regularly and reset if necessary.
Resetting is necessary:
If the quantity deviates by more than 10g from the target value
If the Air-Con Service Station has been shaken, for example during transport
on bumpy roads
Every four to six weeks