Doc.No.: 03118-100-CO
Page 8 of 11
8.4.2 External Control outputs
During General Alarm (EM-PA/PA) some external outputs are activated.
1. Entertainment mute PA / GA Pass/Fail
2. Volume override Pass/Fail
3. GA warning (flashing) lights Pass/Fail
The GA Alarm tone consist of 7 short, 1 long tone bursts. One output is provided for tone
synchronisation and will be turned off (NO) and on (closing) along with the signal tone:
4. GA interface to ships whistle / siren Pass/Fail
8.5 Paging during alarm (General Alarm)
Activating “PA” during alarm will automatically select the EM-PA” functionality.
The alarm tone will be muted during this override.
Check this function. Pass/Fail
8.6 Failure / warning outputs
There are two dry closing contacts voltage for indication of failure and warning conditions:
1. Power failure
Primary and Secondary mains power supply missing
Backup power missing
Pass/Fail
2. General warning
No communication with user panel
Pass/Fail
8.7 Redundancy test
Remove power from “A” system. Ensure all alarms and paging
operates satisfactorily on the “B” system. Restore power on “A” system.
Pass/Fail
Remove power from “B” system. Ensure all alarms and paging
operates satisfactorily on the “A” system. Restore power on “B” system.
Pass/Fail
8.8 Sound Pressure Level
The major requirement of a GA / PA system is sufficient coverage and sound pressure level
(SPL) for alarms and PA messages to be heard throughout the installation. The requirement is a
minimum of 75dBA and at least 10dBA above the ambient noise level. The requirement is
80dBA and at least 10dBA above the ambient noise level in interior and exterior spaces.
Handbook page
58 of 89