SETUP
Page 33
Oil temperature (TC) 5.4.1
5.4.1.1 Maximum value
Defines the switch-on point for the alarm signal.
Setting range: 0...150°C
5.4.1.2 Switching delay
Defines the switch-on delay for the alarm signal.
Setting range: 0...900 s
5.4.1.3 Hysteresis
Defines the hysteresis for the switching point.
Setting range: 1...30 K
Oil level (TC) 5.4.2
Minimum value
Defines the switch-on point for the 'Oil level too low' alarm signal.
Setting range: 0 … 150%
Maximum value
Defines the switch-on point for the 'Oil level too high' alarm signal.
Setting range: 0 … 150%
Switching delay
Defines the switch-on delay for the alarm signal.
Setting range: 0...900 s