SETUP
Page 35
5.5 SETUP 4: Alarm
SETUP 4 is accessed by pressing the '→' arrow or <F1> in
SETUP 3.
Use <F2...F5> to access other submenus in which limits,
switching delays and hysteresis can be selected.
In setup 4 the limits for oil temperature alarm, winding tem-
perature alarm and the winding temperature trip can be ad-
justed.
Oil temperature (Alarm) 5.5.1
Limit value
Defines the switch-on point for the alarm signal.
Setting range: 0...150°C
Switching delay
Defines the switch-on delay for the alarm signal.
Setting range: 0...900 s
Hysteresis
Defines the hysteresis for the switching point.
Setting range: 1...30 K