Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils will
cause high pressure inside the coil
tubing and damage to the coil.
Some chemical coil cleaning
compounds are caustic or toxic. Use
these substances only in accordance
with the manufacturer’s usage
instructions. Failure to follow
instructions may result in equipment
damage, injury or death.
WATER PRESSURE
Prior to connection of condensing
water supply, verify water pressure is
less than maximum pressure shown
on unit nameplate. To prevent injury
or death due to instantaneous release
of high pressure water, relief valves
must be field supplied on system
water piping.
To prevent damage to the unit, do not
use acidic chemical coil cleaners. Do
not use alkaline chemical coil cleaners
with a pH value greater than 8.5, after
mixing, without first using an
aluminum corrosion inhibitor in the
cleaning solution.
Do not use oxygen, acetylene or air in
place of refrigerant and dry nitrogen
for leak testing. A violent explosion
may result causing injury or death.
Always use a pressure regulator,
valves and gauges to control incoming
pressures when pressure testing a
system. Excessive pressure may
cause line ruptures, equipment
damage or an explosion which may
result in injury or death.
Failure to properly drain and vent coils
when not in use during freezing
temperature may result in coil and
equipment damage.
Rotation must be checked on all
MOTORS of 3 phase units at startup
by a qualified service technician.
Check fan motor rotation for proper
operation. Alterations must only be
made at the unit power connection.