266CRx, 266JRx, 266CSx, 266JSx | OI/266CXX/266JXX/HART-EN Rev. B 51
MV Setup - 2 Remote
Seals
MV-Calculation No Calculation
Flow
Level
Level Calculation
Level Unit Steam Drum Level
Open Tank
Closed Tank
Closed Tank, 2 Remote
Seals
Lower Level Dimension b from Fig. 36
Upper Level Dimension d from Fig. 36
Distance process
Connection
Dimension e from Fig. 36
Transm. mount. Pos. Dimension a from Fig. 36
Temperature Unit
Min. Temperature Minimum measuring medium temperature
Max. Temperature Maximum measuring medium temperature
Density Unit
Min. Temp. Density Density of the measuring medium at minimum temperature
Max. Temp. Density Density of the measuring medium at maximum temperature
Temperature Gas Density Reference temperature for specification of the gas density, e.g.
0 C for “standard conditions”.
Static Pressure Unit
Pressure Gas Density Reference pressure for specification of gas density, e.g 1.013
bar for “standard conditions”
Gas Density Gas density for the reference conditions specified above
Capillary Temperatur PT100
Sensor Temperature
Fixed Value
Value Capillary
Temperature
Fill Fluid Halocarbon 4.2, Galden
G5, DC 200, AN 140,
Syltherm, Silicon M5,
Neobee M20, Glycerin
Water, Marcol 122, Silicon
DC704
Restore Last Parameter
Fig. 36: Level measurement with closed tanks with two diaphragm seals
H1 The lower fill level to be measured | H2 The higher fill level to be measured
1 Liquid level | 2 Pressure transmitter | 3 Gas above the fluid | 4 Capillary tube | 5 Diaphragm seal with capillary tube connection