266CRx, 266JRx, 266CSx, 266JSx | OI/266CXX/266JXX/HART-EN Rev. B 67
Error code Displayed message Possible cause Recommended measure Transmitter
reaction
S052.031
Max operating pressure
Exceeded
The static pressure of the process increases
the maximum permissible operating pressure
for the transmitter. Exceeding the maximum
operating pressure can entail mechanical
damage on the process connections
(flanges, pipes, etc.) or cause dangerous
situations.
You must check whether the pressure
transmitter is suitable for the process
conditions.
None
S054.006
Sensor Temperature Out of
Limits
The temperature of the process environment
influences the pressure transmitter. Excess
temperatures can reduce accuracy, impair
device components, and make a calibration
or replacement necessary.
You must check whether the pressure
transmitter is suitable for the process
conditions. A different type of installation
could be necessary, e.g. use of diaphragm
seals.
None