EasyManua.ls Logo

ABB 650 series - Interlocking for Bus-Section Breaker A1 A2_BS; Application; Signals from All Feeders

ABB 650 series
320 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
If there is no second busbar B at the other side of the transformer and therefore no
QB4 disconnector, then the state for QB4 is set to open by setting the appropriate
module inputs as follows:
QB4_OP = 1
QB4_CL = 0
8.3.5 Interlocking for bus-section breaker A1A2_BS
IP14154-1 v2
8.3.5.1 Application
M15110-3 v7
The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-
section circuit breaker between section 1 and 2 according to figure
59. The function
can be used for different busbars, which includes a bus-section circuit breaker.
QA1
WA1 (A1)
QB2
QC4
QB1
QC3
WA2 (A2)
en04000516.vsd
QC2QC1
A1A2_BS
IEC04000516 V1 EN-US
Figure 59: Switchyard layout A1A2_BS
M15111-4 v3
The signals from other bays connected to the module A1A2_BS are described
below.
8.3.5.2 Signals from all feeders
M15111-6 v4
If the busbar is divided by bus-section circuit breakers into bus-sections and both
circuit breakers are closed, the opening of the circuit breaker must be blocked if a
bus-coupler connection exists between busbars on one bus-section side and if on
the other bus-section side a busbar transfer is in progress:
1MRK 511 423-UEN A Section 8
Control
Bay control REC650 2.2 IEC 141
Application manual

Table of Contents

Other manuals for ABB 650 series

Related product manuals