EasyManua.ls Logo

ABB 650 series - Setting Guidelines; Setting Example

ABB 650 series
320 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.13.3 Setting guidelines
GUID-ADA3E806-BEF1-4D15-B270-207386A0AEE4 v2
For proper operation of comparison the set value should be set within the range of
± 2 ×10
9
.
Setting procedure on the IED:
EnaAbs: This setting is used to select the comparison type between signed and
absolute values.
Absolute: Comparison is performed on absolute values of input and reference
values
Signed: Comparison is performed on signed values of input and reference
values.
RefSource: This setting is used to select the reference source between input and
setting for comparison.
Input REF: The function will take reference value from input REF
Set Value: The function will take reference value from setting SetValue
SetValue: This setting is used to set the reference value for comparison when
setting RefSource is selected as SetValue.
9.13.4 Setting example
GUID-13302FD6-1585-42FE-BD6D-44F231982C59 v2
For absolute comparison between inputs:
Set the EnaAbs = Absolute
Set the RefSource = Input REF
Similarly for Signed comparison between inputs
Set the EnaAbs = Signed
Set the RefSource =Input REF
For absolute comparison between input and setting
Set the EnaAbs = Absolute
Set the RefSource = Set Value
SetValue shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Section 9 1MRK 511 423-UEN A
Logic
190 Bay control REC650 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB 650 series

Related product manuals