EasyManuals Logo

ABB 650 series User Manual

ABB 650 series
320 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #162 background imageLoading...
Page #162 background image
QB2OPTR(QB220OTR) (bay 1/sect.B2)
BB_DC_OP
VP_BB_DC
EXDU_BB
en04000509.vsd
QB2OPTR(QB220OTR) (bay n/sect.B2)
. . .
. . .
. . .
VPQB2TR(VQB220TR) (bay 1/sect.B2)
VPQB2TR(VQB220TR) (bay n/sect.B2)
VPDCTR (B1/B2)
EXDU_BB (bay n/sect.B2)
. . .
. . .
. . .
. . .
. . .
. . .
&
&
&
DCOPTR (B1/B2)
EXDU_BB (bay 1/sect.B2)
EXDU_DC (B1/B2)
IEC04000509 V1 EN-US
Figure 80: Signals from any bays in section B2 to a busbar earthing switch in
the same section
For a busbar earthing switch on bypass busbar C, these conditions are valid:
QB7OPTR (bay 1)
BB_DC_OP
VP_BB_DC
EXDU_BB
en04000510.vsd
&
&
&
QB7OPTR (bay n)
. . .
. . .
. . .
VPQB7TR (bay 1)
VPQB7TR (bay n)
EXDU_BB (bay 1)
EXDU_BB (bay n)
. . .
. . .
. . .
. . .
. . .
. . .
IEC04000510 V1 EN-US
Figure 81: Signals from bypass busbar to busbar earthing switch
8.3.7.3 Signals in double-breaker arrangement
M15053-83 v4
The busbar earthing switch is only allowed to operate if all disconnectors of the bus
section are open.
Section 8 1MRK 511 423-UEN A
Control
156 Bay control REC650 2.2 IEC
Application manual

Table of Contents