Appendix F Environmental Data Electromagnetic Compatibility and Main Voltage Conditions
3BSE 027 941 R301 219
Electromagnetic Compatibility and Main Voltage Conditions
Table 73. Electromagnetic Compatibility and Main Voltage Conditions
Environmental Specification
Compliance with
Standard
Environment Factor
Industrial
Environment
Electromagnetic Compatibility Conditions
Emission
–Radiated
–Conducted
Class A EN 55011
Immunity
–Radiated RF field
10V/m EN 61000-4-3
ENV 50 204
Immunity
–Conducted RF field
10V EN 61000-4-3
Immunity
–ESD (Electrical
Discharge)
4 kV contact discharge
8 kV air discharge
EN 61000-4-2
Immunity
–EFT/B (Electrical Fast
Transient/Burst)
2 kV, power ports
1 kV, other lines
EN 61000-4-4
Immunity
–Damped oscillatory
wave
IEC 60255-22-1
Immunity
–Power frequency
magnetic field
30A/m, cont.
3A/m for CRTs
EN 61000-4-8
Immunity
–Surge
2kV, common
1 kV, differential
EN 61000-4-5

Table of Contents