E-Clipse Bypass Configurations for ACH550 Drives 53
Parameter Descriptions
Group 03
Code Name Resolution Range Default Description
0309 ALR WORD 2 b0: not used
b1: not used
b2: Override 1
b3: Override 2
b4: 1 = Start Enable 1
b5: 1 = Start Enable 2
b6: 1 = Start Enable 3
b7: 1 = Start Enable 4
b8: 1 = Mode auto lock
b9: 1 = Mode local lock
b10: 1 = Comm config error
b11: 1 = FIG parameter
configuration
b12: 1 = Drive faulted
b13 - b15: not used
0 Bypass alarm status, word 2
Group 04
Code Name Resolution Range Default Description
0401 LAST FAULT 1 3001 - 3999
See 'Faults' page
0 Last fault declared
0402 F1 TIME 1 1, days ago 0 - 65535 0 Time since last fault, days
0403 F1 TIME 2 2, ago 00:00:00 - 23:59:58 0 Time since last fault, hr:min:sec
0404 F1 VOLTAGE 1V 0 - 1200V 0 Input voltage at last fault
0405 F1
CURRENT
0.1A 0.0 - 6553.5A 0 Motor current at last fault
0406 F1 EVENT 1 See parameter 501 0 Last event status before last fault
0407 F1 E1 TIME 2, before 00:00:00 - 23:59:58 0 Time before last fault of last
event: hr:min:sec if time < 1 day
1, days
before
0 - 9999 days if time >= 1 day
0408 F1 EVENT 2 See parameter 501 0 2nd to last event status before
last fault