E-Clipse Bypass Configurations for ACH550 Drives 55
Parameter Descriptions
Group 05
Code Name Resolution Range Default Description
0501 LAST EVENT b0: 1 = Bypass mode
b1: 1 = Safeties In
b2: 1 = Run Enable
b3: 1 = Start
b4: 1 = In Auto Transfer
b5: 1 = Bypass Override
b6: 1 = Fireman's Override
b7: 1 = Drive Fault
b8: 1 = Bypass Fault
b9: 1 = System Started
b10: 1 = System Running
b11:1 = Drive First Start
Completed
b12: not used
b13: not used
b15,b14: 0,0 = Off; 0,1 =
Hand, 1,0 = Auto; 1,1 = not
valid
0 Status at last event
0502 E1 TIME 1 1, days ago 0 - 65535 0 Time since last event, days
0503 E1 TIME 2 2, ago 00:00:00 - 23:59:58 0 Time since last event, hr:min:sec
0504 EVENT 2 See parameter 501 0 Status of 2nd to last event
0505 E2 TIME 1 1, days ago 0 - 65535 0 Time since 2nd last event, days
0506 E2 TIME 2 2, ago 00:00:00 - 23:59:58 0 Time since 2nd last event,
hr:min:sec
0507 EVENT 3 See parameter 501 0 Status of 3rd to last event
0508 E3 TIME 1 1, days ago 0 - 65535 0 Time since 3rd last event, days
0509 E3 TIME 2 2, ago 00:00:00 - 23:59:58 0 Time since 3rd last event,
hr:min:sec
0510 EVENT 4 See parameter 501 0 Status of 4th to last event
0511 E4 TIME 1 1, days ago 0 - 65535 0 Time since 4th last event, days
0512 E4 TIME 2 2, ago 00:00:00 - 23:59:58 0 Time since 4th last event,
hr:min:sec