EasyManua.ls Logo

ABB ACH550 series - Page 58

ABB ACH550 series
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56 E-Clipse Bypass Configurations for ACH550 Drives
Parameter Descriptions
Group 14
Code Name Resolution Range Default Description
1401 RO1 SELECT 1 0 = NOT SEL
1 = SYS READY
2 = SYS RUNNING
3 = SYS STARTED
4 = BYPASS SEL
5 = BYPASS RUN
6 = BYPASS FLT
7 = BYP NOT FLT
8 = BYPASS ALRM
9 = DRIVE FAULT
10 = DRV NOT FLT
11 = DRIVE ALARM
12 = OVERRIDE
13 = BYPASS HAND
14 = BYPASS OFF
15 = BYPASS AUTO
16 = COMM CTRL
17 = SYS ALARM
18 = BYP FLT/ALM
19 = BYP OVERLD
20 = BYP UNDERLD
21 = PCB OVERTMP
22 = SYS UNDERLD
23 = SYSTEM FLT
24 = SYS FLT/ALM
25 = SYS EXT CTL
26 = SYS OVERLD
27 = CONTACT FLT
BYP NOT
FLT
(7)
Selects function for digital output.
Define the event or condition that
activates relay 1.
1402 R1 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to active
output.
1403 R1 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state to
inactive output.
1404 RO2 SELECT 1 See RO 1 Select. SYS
RUNNING
(2)
1405 R2 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to active
output.
1406 R2 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state to
inactive output.
1407 RO3 SELECT 1 See RO 1 Select. SYS
STARTED
(3)
1408 R3 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to active
output.
1409 R3 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state to
inactive output.
1410 RO4 SELECT 1 See RO 1 Select. BYPASS
SEL
(4)

Table of Contents

Related product manuals