56 E-Clipse Bypass Configurations for ACH550 Drives
Parameter Descriptions
Group 14
Code Name Resolution Range Default Description
1401 RO1 SELECT 1 0 = NOT SEL
1 = SYS READY
2 = SYS RUNNING
3 = SYS STARTED
4 = BYPASS SEL
5 = BYPASS RUN
6 = BYPASS FLT
7 = BYP NOT FLT
8 = BYPASS ALRM
9 = DRIVE FAULT
10 = DRV NOT FLT
11 = DRIVE ALARM
12 = OVERRIDE
13 = BYPASS HAND
14 = BYPASS OFF
15 = BYPASS AUTO
16 = COMM CTRL
17 = SYS ALARM
18 = BYP FLT/ALM
19 = BYP OVERLD
20 = BYP UNDERLD
21 = PCB OVERTMP
22 = SYS UNDERLD
23 = SYSTEM FLT
24 = SYS FLT/ALM
25 = SYS EXT CTL
26 = SYS OVERLD
27 = CONTACT FLT
BYP NOT
FLT
(7)
Selects function for digital output.
Define the event or condition that
activates relay 1.
1402 R1 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to active
output.
1403 R1 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state to
inactive output.
1404 RO2 SELECT 1 See RO 1 Select. SYS
RUNNING
(2)
1405 R2 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to active
output.
1406 R2 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state to
inactive output.
1407 RO3 SELECT 1 See RO 1 Select. SYS
STARTED
(3)
1408 R3 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to active
output.
1409 R3 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state to
inactive output.
1410 RO4 SELECT 1 See RO 1 Select. BYPASS
SEL
(4)