ACH580 E-Clipse bypass and packaged drive user manual 127
Embedded fieldbus
Note: For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays and relinquish
defaults.
Analog input object instance summary – Drive
The following table summarizes the Analog Input Objects supported:
BV25 STO MON This object indicates the drive’s
Safe Torque Off status.
ON/OFF R
BV26 UL MON This object indicates the drive’s
underload status.
ON/OFF R
BV27 OL MON This object indicates the drive’s
overload status.
ON/OFF R
BV28 MTR HTG CMD This object activates the drive’s
motor pre-heating function.
ON/OFF W
BV29 MTR HG MON This object indicates the drive’s
motor pre-heating status.
ON/OFF R
BV30 USER0 MON This object indicates the drive’s
User Bit0 status.
ON/OFF R
BV31 USER1 MON This object indicates the drive’s
User Bit1 status.
ON/OFF R
BV32 USER2 MON This object indicates the drive’s
User Bit2 status.
ON/OFF R
BV33 USER3 MON This object indicates the drive’s
User Bit3 status.
ON/OFF R
BV34 USER0 CMD This object activates the drive’s
User Bit0.
ON/OFF C
BV35 USER1 CMD This object activates the drive’s
User Bit1.
ON/OFF C
BV36 USER2 CMD This object activates the drive’s
User Bit2.
ON/OFF C
BV37 USER3 CMD This object activates the drive’s
User Bit3.
ON/OFF C
BV39 PAR SAV CMD This object triggers the drive to
save parameters to non-volatile
memory.
SAVE/DONE W
BV40 PID SET2 SEL This object selects which PID
gain set is active.
SET2/SET1 W
Instance
ID
Object Name Description Units
Present Value
Access Type
AI0 ANALOG INPUT 1 This object indicates the value of
Analog Input 1. The corresponding
drive parameter is 12.101.
Percent R
AI1 ANALOG INPUT 2 This object indicates the value of
Analog Input 2. The corresponding
drive parameter is 12.102.
Percent R
Instance
ID
Object Name Description
Active/Inactive
Text
Present Value
Access Type