Loading...
ACH580 E-Clipse bypass and packaged drive user manual 201
Technical data
Technical data
Vertical enclosure terminals maximum wire size and terminal torque values
Type Code
1
Nominal Output
Ratings
Frame
Size
Maximum Wire Size and Terminal Torque
Drive
Current
Package
Power
Circuit
Breaker
Disconnect
Switch
Motor
Termination
Ground
Lugs
AHP
208/230 Volts
ACH580-VxR-04A6-2 4.6 1 R1
#10
62 in-lbs
#10
55 in-lbs
#6
11-13 in-lbs
#4
35 in-lbs
ACH580-VxR-06A6-2 6.6 1.5 R1
ACH580-VxR-07A5-2 7.5 2 R1
ACH580-VxR-10A6-2 10.6 3 R1
ACH580-VxR-017A-2 16.7 5 R1
#8
62 in-lbs
#6
55 in-lbs
ACH580-VxR-024A-2 24.2 7.5 R2
ACH580-VxR-031A-2 30.8 10 R2
#4
55 in-lbs
#1
35 in-lbs
#2
50 in-lbs
ACH580-VxR-046A-2 46.2 15 R3
#2
62 in-lbs
#2
55 in-lbs
#2/0
110 in-lbs
ACH580-VxR-059A-2 59.4 20 R3
#1
55 in-lbs
ACH580-VxR-075A-2 74.8 25 R4
#1/0
75 in-lbs
1) “VxR” represents both VCR and VDR.
Type Code
1
Nominal Output
Ratings
Frame
Size
Maximum Wire Size and Terminal Torque
Drive
Current
Package
Power
Circuit
Breaker
Disconnect
Switch
Motor
Termination
Ground
Lugs
AHP
460 Volts
ACH580-VxR-02A1-4 2.1 1 R1
#12
62 in-lbs
#10
55 in-lbs
#6
11-13 in-lbs
#4
35 in-lbs
ACH580-VxR-03A0-4 3.0 1.5 R1
ACH580-VxR-03A5-4 3.5 2 R1
ACH580-VxR-04A8-4 4.8 3 R1
ACH580-VxR-07A6-4 7.6 5 R1
ACH580-VxR-012A-4 12 7.5 R1
ACH580-VxR-014A-4 14 10 R2
#10
62 in-lbs
#8
55 in-lbs
ACH580-VxR-023A-4 23 15 R2
#6
55 in-lbs
ACH580-VxR-027A-4 27 20 R3
#8
62 in-lbs
#4
55 in-lbs
#1
35 in-lbs
#2
50 in-lbs
ACH580-VxR-034A-4 34 25 R3
#3
55 in-lbs
ACH580-VxR-044A-4 44 30 R3
ACH580-VxR-052A-4 52 40 R4
#2
62 in-lbs
#2
55 in-lbs
#2/0
110 in-lbs
ACH580-VxR-065A-4 65 50 R4
#1
55 in-lbs
ACH580-VxR-077A-4 77 60 R4
#1/0
75 in-lbs