238 ACH580 E-Clipse bypass and packaged drive user manual
Technical data
460 Volt
Output
Ratings
Base
Drive
Frame
Size
Maximum Power Wiring Data
Type Code
1
AHP
Circuit
Breaker
UL
(NEMA)
Type 1
and 12
Circuit
Breaker
UL
(NEMA)
Type 3R
Disconnect
Switch
UL (NEMA)
Type 1
and 12
Disconnec
t Switch
UL (NEMA)
Type 3R
Motor
Terminals
Ground
Lugs
UL
(NEMA)
Type 1
and 12
Ground
Lugs
UL
(NEMA)
Type 3R
ACH580-PxR-02A1-4 2.1 1 R1
#12
62 in-lbs
#12
62 in-lbs
#10
55 in-lbs
#10
55 in-lbs
#10
0.7 ft-lbs
#2
50 in-lbs
#2
50 in-lbs
ACH580-PxR-03A0-4 3 1.5 R1
ACH580-PxR-03A5-4 3.5 2 R1
ACH580-PxR-04A8-4 4.8 3 R1
ACH580-PxR-07A6-4 7.6 5 R1
ACH580-PxR-012A-4 12 7.5 R1
ACH580-PxR-014A-4 14 10 R2
#10
62 in-lbs
#10
62 in-lbs
#8
55 in-lbs
#8
55 in-lbs
#6
1.1 ft-lbs
ACH580-PxR-023A-4 23 15 R2
#6
55 in-lbs
#6
55 in-lbs
ACH580-PxR-027A-4 27 20 R3
#8
62 in-lbs
#8
62 in-lbs
#4
55 in-lbs
#4
55 in-lbs
#2
2.6 ft-lbsACH580-PxR-034A-4 34 25 R3
#6
62 in-lbs
#6
62 in-lbs
#3
55 in-lbs
#3
55 in-lbs
ACH580-PxR-044A-4 44 30 R3
ACH580-PxR-052A-4 52 40 R4
#1/0
124 in-lbs
#2
55 in-lbs
#2
55 in-lbs
#1
3.0 ft-lbs
ACH580-PxR-065A-4 65 50 R4
#1/0
124 in-lbs
#1/0
124 in-lbs
#1
55 in-lbs
#1
55 in-lbs
ACH580-PxR-077A-4 77 60 R4
#1/0
55 in-lbs
#1/0
55 in-lbs
ACH580-PxR-096A-4 96 75 R5
#1/0
124 in-lbs
Consult
Factory
#3/0
275 in-lbs
Consult
Factory
#2/0
4.1 ft-lbs
3 x #3/0
250 in-lbs
Consult
Factory
ACH580-PxR-124A-4 124 100 R6
#2/0
124 in-lbs
250 MCM
275 in-lbs
300 MCM
22.1 ft-lbs
ACH580-PxR-156A-4 156 125 R7
#3/0
124 in-lbs
300 MCM
275 in-lbs
500 MCM
29.5 ft-lbs
ACH580-PxR-180A-4 180 150 R7
#4/0
124 in-lbs
ACH580-PxR-240A-4 240 200 R8
350
MCM
274 in-lbs
2 x 500
MCM
274 in-lbs
2 x 300
MCM
29.6 ft-lbs
1) “PxR” represents both PCR and PDR.