ACH580 E-Clipse bypass and packaged drive user manual 85
Embedded fieldbus
Note: After any changes to the communication settings, the communication channel
must be reset by either cycling the system power, or by clearing (set to 0 and enter)
and then restoring the station ID (5002) to desired station ID.
Activate drive control functions – EFB
Controlling the drive
Fieldbus control of various drive functions requires configuration to:
Tell the drive (via the bypass) to accept fieldbus control of the function.
Define as a fieldbus input, any drive data required for control.
Define as a fieldbus output, any control data required by the drive.
The following sections describe, at a general level, the configuration required for
each control function. For the protocol-specific details, see the specific protocol
technical data section in this manual.
Start/stop control (Drive only)
Using the fieldbus for start/stop control of the drive only requires:
Bypass parameter values set as defined below.
Fieldbus controller supplied command(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Control commands must be addressed to the Drive node with parameter 1625 set
to 0 (
DRIVE ONLY). For SYSTEM control refer to Start/stop control (System) on
page 91.
5099 BY OB ID H
BACnet Device object ID upper
word. See parameter 5040 for
description of how to use this
parameter.
N/A N/A Resolution: 1
Range: 0-419
Default: 0
Bypass
Parameter
Value Description
Protocol Reference
Modbus
1
N2
BACnet
ABB DRV
DCU
PROFILE
1601 START/
STOP
2 (COMM) Start/Stop by
fieldbus with Ext1
or Ext2 selected.
40001 bits
0…3 (see
page 150)
40031 bits
0, 1 (see
page 151)
BO1 BV10
1625 COMM
CTRL
0 (DRIVE
ONLY)
Enable drive only
control.
N/A
1) For Modbus, the protocol reference can depend on the profile used, hence two columns in
these tables. One column refers to the ABB Drives profile, selected when parameter 5825 = 0
(ABB DRV LIM) or 5825 = 2 (ABB DRV FULL). The other column refers to the DCU profile
selected when parameter 5825 = 1 (DCU PROFILE). See ABB control profiles technical data –
Drive section on page 146.
Bypass
Parameter
Description
EFB Protocol Reference
Modbus N2 BACnet