134 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
BACnet input object instance summary – Bypass
The following table summarizes the Binary Input Objects supported:
Note: For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays and relinquish
defaults.
BACnet output object instance summary – Bypass
The following table summarizes the Binary Output Objects supported:
Instance
ID
Object
Name
Description
Active/
Inactive Text
Present Value
Access Type
BI0 RO 1 ACT This object indicates the status of
bypass Relay Output 1.
ON/OFF R
BI1 RO 2 ACT This object indicates the status of
bypass Relay Output 2.
ON/OFF R
BI2 RO 3 ACT This object indicates the status of
bypass Relay Output 3.
ON/OFF R
BI3 RO 4 ACT This object indicates the status of
bypass Relay Output 4.
ON/OFF R
BI4 RO 5 ACT This object indicates the status of
bypass Relay Output 5.
ON/OFF R
BI5 DI 1 ACT This object indicates the status of
bypass Digital Input 1.
ON/OFF R
BI6 DI 2 ACT This object indicates the status of
bypass Digital Input 2.
ON/OFF R
BI7 DI 3 ACT This object indicates the status of
bypass Digital Input 3.
ON/OFF R
BI8 DI 4 ACT This object indicates the status of
bypass Digital Input 4.
ON/OFF R
BI9 DI 5 ACT This object indicates the status of
bypass Digital Input 5.
ON/OFF R
BI10 DI 6 ACT This object indicates the status of
bypass Digital Input 6.
ON/OFF R
Instance
ID
Object Name Description
Active/
Inactive Text
Present Value
Access Type
BO0 RO1 COMMAND This object controls the output state
of bypass Relay Output 1. This
control requires that parameter
1401 value =
COMM.
ON/OFF C
BO1 RO2 COMMAND This object controls the output state
of bypass Relay Output 2. This
control requires that parameter
1404 value =
COMM.
ON/OFF C
BO2 RO3 COMMAND This object controls the output state
of bypass Relay Output 3. This
control requires that parameter
1407 value =
COMM.
ON/OFF C