158 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
MODBUS addressing – Bypass
0xxxx Registers
MODBUS addressing of 0xxxx registers maps the Bypass Control Word shown in
the following table to the first 16 coils when using the bypass device ID. The coil
number is the bit number plus 1. In other words, bits 0-31 are mapped to 1-32.
Relay output control is possible on the bypass by using coils 33-37 and the bypass
device ID. Relay control on the drive is described in the 0xxxx mapping subsection of
the Modbus addressing section for the drive device ID on page 139.
These registers are summarized in the following tables. Reminder: stop and enable
related bits are valid at only one device subject to the status of bypass
parameter 1625, COMM CTRL.
MODBUS Registers (0xxxx)
MODBUS Ref. Bit
Bypass Device ID
BCU PROFILE
00001 0 START
00002 1 RESET
00003 2 RUN_DISABLE
00004 3 FBLOCAL_CTL
00005 4 START_DISABLE1
00006 5 START_DISABLE2
00007 6 START_DISABLE3
00008 7 START_DISABLE4
00009 8 OVERRIDE
00010 9 LINK_ON
00011 10 N/A
00012 11 N/A
00013 12 N/A
00014 13 N/A
00015 14 N/A
00016 15 N/A
00017 16 N/A
00018 17 N/A
00019 18 N/A
00020 19 N/A
00021...00032 20-31 N/A
00033 Bypass Relay Output 1
00034 Bypass Relay Output 2
00035 Bypass Relay Output 3
00036 Bypass Relay Output 4
00037 Bypass Relay Output 5
00038 N/A