160 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
4xxxxx Registers – Bypass
MODBUS addressing of 4xxxxx registers maps the drive’s parameters and other
values when using the drive device ID. The bypass’s parameters and other values
are mapped when using the bypass device ID.
Registers 400001 … 400099 - Bypass
The bypass maps its parameters and other data to the 4xxxxx holding registers as
follows:
400001...400099 map to bypass control and actual values. These registers are
descibed in the table below.
400267...465535 map to bypass parameters 0101...255255. Register addresses
that do not correspond to bypass parameters are invalid. If there is an attempt to
read or write outside the parameters addresses, the Modbus interface returns an
exception code to the controller.
Register addressing is done as follows: Use 400000 + 256 * (parameter group) +
parameter index.
For example: bypass parameter 0111 would be mapped to 400000 + 256 *
1 = 400267.
The following table summarizes the 4xxxxx bypass control registers
400001...400099:
Note: All parameters referenced are bypass parameters.
10030 29
10031 30
10032 31
10033 Bypass DI1
10034 Bypass DI2
10035 Bypass DI3
10036 Bypass DI4
10037 Bypass DI5
10038 Bypass DI6
MODBUS Registers (40001 to 40099)
MODBUS Ref.
Internal location
(All profiles)
Bypass Device ID
400001 Control Word Maps directly to BCU profile
control word.
400004 Status Word Maps directly to BCU profile
status word.
1.1.1 MODBUS Registers (1xxxx)
MODBUS Ref. Bit
Bypass Device ID
BCU PROFILE

Table of Contents