ACH580 E-Clipse bypass and packaged drive user manual 171
Fieldbus adapter
Start/stop direction control
Using the fieldbus for start/stop control of the system requires:
• Bypass parameter values set as defined below.
• Fieldbus controller supplied command(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Miscellaneous system control
Note: Control of system commands is dependent upon the setting of bypass
parameter 1625.
Using the fieldbus miscellaneous system control requires:
• Bypass parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Bypass Parameter Value Description
Protocol Reference
Modbus TCP
1
ABB DRV DCU PROFILE
1601 START/STOP 2 (COMM) Start/Stop by fieldbus with
Ext1 or Ext2 selected.
400001 bits
0…3
40031 bits 0, 1
1625 COMM CTRL 1 (SYSTEM) Enable system control. N/A
1) For Modbus TCP, the protocol reference can depend on the profile used, hence two columns in
these tables. One column refers to the ABB Drives profile, selected when parameter 51.02 = 0
(ABB Drives-Classic) or 51.02 = 1 (ABB Drives-Enhanced). The other column refers to the DCU
profile selected when parameter 51.02 = 2 (Transparent-16-Bit). See ABB drives profile technical
data section on page 175.
Bypass Parameter Value Setting
Protocol
Reference
Modbus TCP
1602 RUN PERMISSIVE 2 (COMM)
(Not Recommended)
Run permissive by
fieldbus.
400001 bit 2
1603 START INTERLOCK 1 2 (COMM)
(Not Recommended)
Source for Start
Interlock 1 is the
fieldbus Command
word.
400001 bit 4
1604 START INTERLOCK 2 2 (COMM)
(Not Recommended)
Source for Start
Interlock 2 is the
fieldbus Command
word.
400001 bit 5
1605 START INTERLOCK 3 2 (COMM)
(Not Recommended)
400001 bit 6
1606 START INTERLOCK 4 2 (COMM)
(Not Recommended)
400001 bit 7
1607 START RESET SEL 2 (COMM) Fault reset by fieldbus 400001 bit 1
1625 COMM CTROL 1 (SYSTEM) Enable System Control. N/A