ACH580 E-Clipse bypass and packaged drive user manual 171
Fieldbus adapter
Start/stop direction control
Using the fieldbus for start/stop control of the system requires:
Bypass parameter values set as defined below.
Fieldbus controller supplied command(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Miscellaneous system control
Note: Control of system commands is dependent upon the setting of bypass
parameter 1625.
Using the fieldbus miscellaneous system control requires:
Bypass parameter values set as defined below.
Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Bypass Parameter Value Description
Protocol Reference
Modbus TCP
1
ABB DRV DCU PROFILE
1601 START/STOP 2 (COMM) Start/Stop by fieldbus with
Ext1 or Ext2 selected.
400001 bits
0…3
40031 bits 0, 1
1625 COMM CTRL 1 (SYSTEM) Enable system control. N/A
1) For Modbus TCP, the protocol reference can depend on the profile used, hence two columns in
these tables. One column refers to the ABB Drives profile, selected when parameter 51.02 = 0
(ABB Drives-Classic) or 51.02 = 1 (ABB Drives-Enhanced). The other column refers to the DCU
profile selected when parameter 51.02 = 2 (Transparent-16-Bit). See ABB drives profile technical
data section on page 175.
Bypass Parameter Value Setting
Protocol
Reference
Modbus TCP
1602 RUN PERMISSIVE 2 (COMM)
(Not Recommended)
Run permissive by
fieldbus.
400001 bit 2
1603 START INTERLOCK 1 2 (COMM)
(Not Recommended)
Source for Start
Interlock 1 is the
fieldbus Command
word.
400001 bit 4
1604 START INTERLOCK 2 2 (COMM)
(Not Recommended)
Source for Start
Interlock 2 is the
fieldbus Command
word.
400001 bit 5
1605 START INTERLOCK 3 2 (COMM)
(Not Recommended)
400001 bit 6
1606 START INTERLOCK 4 2 (COMM)
(Not Recommended)
400001 bit 7
1607 START RESET SEL 2 (COMM) Fault reset by fieldbus 400001 bit 1
1625 COMM CTROL 1 (SYSTEM) Enable System Control. N/A