Loading...
ACH580 E-Clipse bypass and packaged drive user manual 233
Installation
PB1/PB2
ACH580 Drive
Disconnect
Output
Ground Lug
Input
Terminals
Input
Ground Lug
Motor
Terminals
Switch or
Circuit
T1 T2 T3
The alternate (HI) setting further reduces the likeli-
hood of condensate in high humidity environments.
RHTR Temperature
HI/LO Jumber (X1)
Heater ON
Temperature
Heater OFF
Temperature
Default Setting
(X1 jumper in LO
position)
14.4 °C
58 °F
21.4 °C
70.5 °F
Alternate Setting
(X1 jumper in HI
position)
17.8 °C
64 °F
24.4 °C
76.5 °F
(PxB3R-1, PxB3R-2)
Motor
Terminals
Motor
Ground Lug
Line Reactor
(Optional)
Breaker
Service
Switch
(Optional)
Fuses