ACH580 E-Clipse bypass and packaged drive user manual 77
Embedded fieldbus
Do not directly ground the EIA 485 network at any point. Ground all devices on
the network using their corresponding earthing terminals.
As always, the grounding wires should not form any closed loops, and all the
devices should be earthed to a common ground.
Connect the EIA 485 link in a daisy-chained bus, without dropout lines.
Do not connect the shield at the bypass. Tie the shields together at the bypass.
Only load the shield connection at the EIA 485 master.
For configuration information see the following:
Communication setup – EFB section.
Activate drive control functions – EFB section.
The appropriate EFB protocol specific technical data.
To reduce noise on the network, terminate the EIA 485 network using 120
resistors at both ends of the network. Use the DIP switch to connect or
disconnect the termination resistors. Refer to page 78 for the diagram and
table.