ACH580 E-Clipse bypass and packaged drive user manual 83
Embedded fieldbus
Note: After any changes to the communication settings, the communication channel
must be reset by either cycling the system power, or by clearing (set to 0 and enter)
and then restoring the station ID (5803) to desired station ID.
5840 DV OB ID L
BACnet Device object ID lower
word.
The Drive’s Device object ID
must be unique across all
BACnet devices in the building
network. Valid values are
0…4194302. The Device
Object ID is formed as a
combination of parameter 5840
and 5899. To set an ID from 1
to 65535 set this parameter =
to the desired ID and set 5899
= 0. To set an ID greater than
65535, set this parameter to
the lower 4 digits of the ID and
set 58.99 to the remaining
upper digits. For example, to
set the ID to 71234, set the
5840 = 1234 and 5899 = 7. The
default values of 5840 = 0 and
5899 = 0 are handled specially.
This case uses parameter
5803, the MAC ID as the value
for the device object ID.
N/A
N/A
Resolution: 1
Range: 0-65535
Default: 0
5841 MAX MASTER
The Drive’s highest master
address for devices on the
BACnet MS/TP bus.
Resolution: 1
Range: 0-127
Default: 127
5842 MAX INF FR
The maximum number of
information frames the drive
may transmit before it must
pass the token.
Resolution: 1
Range: 0-10
Default: 1
5899 DV OB ID H
BACnet Device object ID upper
word. See parameter 5840 for
description of how to use this
parameter.
Resolution: 1
Range: 0-419
Default: 0
58100 DB REV
BACnet Database Revision
Resolution: 1
Range: 0-65535
Default: 0