88 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
PID control setpoint source 
Using the fieldbus for the PID control setpoint requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied setpoint value in the appropriate location. (As defined 
in Analog output control)
Drive Parameter Value Setting
Protocol Reference
Modbus
N2 BACnet
ABB 
DRV
DCU 
PROFILE
13.12 AO1 Source 37, AO1 Data Storage Analog Output 1 
controlled by writing to 
parameter 13.91.
–––
13.91 AO1 Data Storage – 403419 AO14 AO0
13.22 AO2 Content Sel 38, AO2 Data Storage Analog Output 2 
controlled by writing to 
parameter 13.92.
–––
13.92 AO2 Data Storage – 403420 AO15 AO1
Drive Parameter Value Description Protocol Reference
40.16 Set 1 setpoint 1 
source
24 (Setpoint data 
storage)
Communication channel setpoint 
source
–
40.17 Set 1 setpoint 2 
source
3 (AI1 scaled) Optional analog input value. Needed if 
combining communication reference 
with analog input value
–
40.18 Set 1 setpoint 
function
0 (In1)
1 (In1+In2)
3 (In1*In2)
Setpoint is 40.92 value itself/+AI1/*AI1 –
NOTE: For 41.16 – 41.18, PID set 2 can be used. Setpoint data storage still uses 40.92, even when PID set 2 is used.