data word. Data words are displayed on the panel
No. Name/Value Description FbEq
Bit Name Value Status
0 RDY_ON 1 Ready to switch on.
0 Not ready to switch on.
1 RDY_ REF 1 Operation enabled.
0 Operation inhibited.
2 RUNNING 1 Drive is modulating.
0 Drive is not modulating.
3 FAULT 1 Drive is in fault state.
0 Drive is not in a fault state.
4 DRY_RUN 1 Dry run fault is detected.
0 No dry run fault.
5 DC_OVERVOLT 1 Excessive intermediate circuit DC voltage
detected.
0 No excessive intermediate circuit DC
voltage.
6 DC_UNDERVOLT 1 Intermediate circuit DC voltage is not
sufficient.
0 Intermediate circuit DC voltage is sufficient.
7 PUMP_MINIMUM_SPEED 1 Minimum speed alarm is active.
0 Minimum speed alarm is not active.
8 SHORT_CIRC 1 Short circuit in motor cable(s), motor or
internal fault of the drive.
0 No short circuit.
9 EARTH_FAULT 1 Earth (ground) fault in motor or motor cable
detected by drive.
0 No earth (ground) fault.
10 MOTOR_PHASE 1 Motor circuit fault due to missing motor
phase.
0 No motor circuit fault.