38 Actual signals and parameters
0185 CUMULA YEAR
FLOW
Shows the measured flow of current year in cubic
decameter. The value displayed is the measured
flow from first
day to current day of the year.
Note: You can reset this value using 6131 RESET
FLOW.
1 = 1 m
6
03 FB ACTUAL SIGNALS
Data words for monitoring the fieldbus
communication (read-only). Each signal is a 16-bit
data word. Data words are displayed on the panel
in hexadecimal format.
0310 SOLAR STS WORD1 A 16-bit data word. 1 = 1
Actual signals
No. Name/Value Description FbEq
Bit Name Value Status
0 RDY_ON 1 Ready to switch on.
0 Not ready to switch on.
1 RDY_ REF 1 Operation enabled.
0 Operation inhibited.
2 RUNNING 1 Drive is modulating.
0 Drive is not modulating.
3 FAULT 1 Drive is in fault state.
0 Drive is not in a fault state.
4 DRY_RUN 1 Dry run fault is detected.
0 No dry run fault.
5 DC_OVERVOLT 1 Excessive intermediate circuit DC voltage
detected.
0 No excessive intermediate circuit DC
voltage.
6 DC_UNDERVOLT 1 Intermediate circuit DC voltage is not
sufficient.
0 Intermediate circuit DC voltage is sufficient.
7 PUMP_MINIMUM_SPEED 1 Minimum speed alarm is active.
0 Minimum speed alarm is not active.
8 SHORT_CIRC 1 Short circuit in motor cable(s), motor or
internal fault of the drive.
0 No short circuit.
9 EARTH_FAULT 1 Earth (ground) fault in motor or motor cable
detected by drive.
0 No earth (ground) fault.
10 MOTOR_PHASE 1 Motor circuit fault due to missing motor
phase.
0 No motor circuit fault.