DefaultUnitRange/ListNameIndex
0.00PID unit 1-200000.00 …
200000.00
Set 2 internal setpoint 141.21
0.00PID unit 1-200000.00 …
200000.00
Set 2 internal setpoint 241.22
0.00PID unit 1-200000.00 …
200000.00
Set 2 internal setpoint 341.23
0.00PID unit 1-200000.00 …
200000.00
Set 1 internal setpoint 041.24
0.00PID unit 1-200000.00 …
200000.00
Set 2 setpoint min41.26
200000.00PID unit 1-200000.00 …
200000.00
Set 2 setpoint max41.27
0.0s0.0 … 1800.0Set 2 setpoint increase time41.28
0.0s0.0 … 1800.0Set 2 setpoint decrease
time
41.29
Not selected[0]-See parameter 40.30
Set 1 setpoint freeze
enable
Set 2 setpoint freeze enable41.30
Not inverted (Ref
- Fbk)[0]
-See parameter 40.31
Set 1 tracking mode
Set 2 deviation inversion41.31
1.00-0.01 … 100.00Set 2 gain41.32
60.0s0.0 … 9999.0Set 2 integration time41.33
0.000s0.000 … 10.000Set 2 derivation time41.34
0.0s0.0 … 10.0Set 2 derivation filter time41.35
0.00--200000.00 …
200000.00
Set 2 output min41.36
100.00--200000.00 …
200000.00
Set 2 output max41.37
Not selected[0]-See parameter 40.38
Set 1 output freeze en-
able
Set 2 output freeze enable41.38
0.00-0.00 … 200000.00Set 1 deadband range41.39
0.0s0.0 … 3600.0Set 1 deadband delay41.40
0.0-0.0 … 200000.0Set 2 sleep level41.43
60.0s0.0 … 3600.0Set 2 sleep delay41.44