Loading...
For information on reforming the capacitors, see
Converter module capacitor
reforming instructions
(3BFE64059629 [English]).
Select the power cables
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive. See Ratings (page 127).
Ensure the cooling
The maximum ambient temperature without derating is:
50 °C (+122 °F) for R0...R2 frames
40 °C (+104 °F) for R3...R8 frames
No condensation or frost is allowed. For more information on the ambient
temperature, see the hardware manual.
Protect the drive and input power cable
If you use gG fuses, make sure that the operating time of the fuse is below 0.5
seconds. Follow the local regulations.