What to doCauseFault / Aux.
code aux code
visible only on
assistant con-
trol panel and
drive com-
poser))
Code
(hex)
Connect motor cable.
If the drive is in scalar mode and
nominal current of the motor is less
than 1/6 of the nominal output
current of the drive, set parameter
31.19 Motor phase loss to No action
[0].
Motor circuit fault due to
missing motor connection
(any of the three phases
not connected). In scalar
control mode, the drive
detects fault only when
the output frequency is
above 10% of the motor
nominal frequency. Con-
nect motor cable. If the
drive is in scalar mode and
nominal current of the
motor is less than 1/6 of
the nominal output cur-
rent of the drive, set para-
meter 31.19 Motor phase
loss to No action [0].
Output phase
loss
3381
Check proper cooling of the drive
and auxiliary cooling fan.
Control board temperat-
ure is too high.
Control board
temperature
4110
Check ambient conditions, air flow
and fan, dust pick-up in heatsink
fins and motor power.
Estimated drive IGBT
temperature is excessive.
IGBT overtemper-
ature
4210
Check ambient temperature, air
flow and fan operation, dust pick-
up in heatsink. Clean whenever ne-
cessary.
Drive module temperature
is excessive.
Cooling4290
Check ambient conditions, air flow
and fan, dust pick-up in heatsink
fins and motor power.
Drive IGBT temperature is
excessive.
IGBT temperat-
ure
42F1
Check ambient conditions, air flow
and fan, dust pick-up in heatsink
fins and motor power.
Power unit module temper-
ature is excessive.
Excess temperat-
ure
4310
Check motor cabling and drive
module(s) cooling.
High temperature differ-
ence between the IGBTs
of different phases.
Excess temperat-
ure difference
4380
Check parameter 35.02 Measured
temperature 1, motor cooling and
fault limit for measured temperat-
ure 1.
Measured temperature 1
has exceeded fault limit.
External temper-
ature 1
4981
Diagnostics 157