8. Connect the twisted shield to the grounding terminal (7b).
9. For R3, connect the conductors to the R+ and R- terminals (7c).
10. Tighten to the torque given below.
R3Frame size
lbf.ftN.m
1.8...3.32.5...4.5R+, R-
7c
7b
7a
Finalization
11. Install the grounding shelf for the control cables (included with the mounting
screws in a plastic bag in the delivery) onto the grounding shelf for the power
cables.
Electrical installation 85
Finalization
11. Install the grounding shelf for the control cables (included with the mounting
screws in a plastic bag in the delivery) onto the grounding shelf for the power
cables.
12. Ground the motor cable shield at the motor end. For minimum radio frequency
interference, ground the motor cable shield 360 degrees at the lead-through of
the motor terminal box.
8
18 EN - Quick installation and start-up guide