EasyManua.ls Logo

ABB ACS560 - Page 64

ABB ACS560
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DefaultUnitRange/ListNameIndex
Speed ref safe[4]Warning [2]No action[0]
Last speed[3]Fault[1]
0b0000-0b000...0b1111AI supervision selection12.04
NameBitNameBitNameBit
Reserved4...15AI2 < MIN2AI1 < MIN0
AI2 > MAX3AI1 > MAX1
0V0.000…11.000AI1 actual value12.11
0--32768.000
32767.000
AI1 scaled value12.12
0V0.000…11.000AI1 forced value12.13
V[2]-V[2], mA[10]AI1 unit selection12.15
0.100s0.000 30.000AI1 filter time12.16
0.000V0.000…11.000AI1 Min12.17
10.000V0.000…11.000AI1 Max12.18
0.000--32768.000
32767.000
AI1 scaled at AI1 Min12.19
50.000--32768.000
32767.000
AI1 scaled at AI1 Max12.20
0.000mA0.000…22.000AI2 actual value12.21
0.000--32768.000
32767.000
AI2 scaled value12.22
0.000mA0.000…22.000AI2 forced value12.23
mA-V[2], mA[10]AI2 unit selection12.25
0.100s0.000 30.000AI2 filter time12.26
4.000mA0.000…22.000AI2 Min12.27
20.000mA0.000…22.000AI2 Max12.28
0.000--32768.000
32767.000
AI2 scaled at AI2 Min12.29
50.000--32768.000
32767.000
AI2 scaled at AI2 Max12.30
64 Parameter listing