Technical data
116
UL class T and L fuses
Dimensions, weights and free space requirements
H height
W1 width of the basic unit with PE terminal (bookshelf)
W2 width with the cable connection terminal plates on the left side only (bookshelf)
(width with the cable connection terminal plates on both sides is 776 mm)
D depth without fastening brackets
(bookshelf mounting: depth with fastening brackets is 571 mm)
W3 width of the basic unit with PE terminal/busbar (flat)
W4 width with the cable connection terminal plates (flat)
For requirements of free space around the drive module, see 43.
Drive type
ACS850-04…
Input
current
Fuse
A A V Manufacturer Type UL class
-430A-5 423 500 600 Bussmann JJS-500 T
-521A-5 501 600 600 Bussmann JJS-600 T
-602A-5 581 800 600 Ferraz A4BY800 L
-693A-5 674 800 600 Ferraz A4BY800 L
-720A-5 705 800 600 Ferraz A4BY800 L
Note 1: See also Implementing thermal overload and short-circuit protection on page
69.
Note 2: In multicable installations, install only one fuse per phase (not one fuse per
conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the
melting curve of the fuse does not exceed the melting curve of the fuse mentioned in the
table.
00581898
IP00 Weight
Busbars on the long side
(bookshelf)
Busbars on the short side (flat)
HW1W2D HW3W4D
mm mm mm mm mm mm mm mm kg
1564 415 562 568 1596 607 779 403 200
UL type open Weight
Height W1 W2 Depth
in. in. in. in. lb
61.57 16.35 22.14 22.36 441