120 Parameters
01.64 Abs motor torque Absolute value of 01.10 Motor torque.-
0.0 … 1600.0% Motor torque. See par.
46.03
01.65 Abs output power Absolute value of 01.14 Output power.-
0.00 … 32767.00
kW or hp
Output power. 1 = 1 unit
01.66 Abs output power %
motor nom
Absolute value of 01.15 Output power % of motor nom.-
0.00 … 300.00% Output power. 10 = 1%
01.68 Abs motor shaft
power
Absolute value of 01.17 Motor shaft power.-
0.00 … 32767.00
kW or hp
Motor shaft power. 1 = 1 unit
01.70 Ambient
temperature %
Measured temperature of incoming cooling air.
The amplitude range of 0…100% corresponds to 0…60 °C or
32…140 °F.
See also 01.31 Ambient temperature.
-
-200.00 … 200.00% Cooling air temperature. 1 = 1%
01.71 Step-up motor
current
Estimated motor current in A when a step-up transformer is in
use. The value is calculated from parameter 01.07 using the
step-up transformer ratio (95.40) and sine filter values 99.18
and 99.19.
-
0.00 … 30000.00 A Estimated motor current. See par.
46.05
01.72 U-phase RMS
current
U-phase rms current. -
0.00 … 30000.00 A U-phase rms current. See par.
46.05
01.73 V-phase RMS
current
V-phase rms current. -
0.00 … 30000.00 A V-phase rms current. See par.
46.05
01.74 W-phase RMS
current
W-phase rms current. -
0.00 … 30000.00 A W-phase rms current. See par.
46.05
01.102 Line current (Only visible when IGBT supply unit control activated by
95.20)
Estimated line current flowing through the supply unit.
-
0.00 … 30000.00 A Estimated line current. See par.
46.05
01.104 Active current (Only visible when IGBT supply unit control activated by
95.20)
Estimated active current flowing through the supply unit.
-
0.00 … 30000.00 A Estimated active current. See par.
46.05
No. Name/Value Description Def/FbEq16