414 Parameters
95.15 Special HW
settings
Contains hardware-related settings that can be enabled and
disabled by toggling the specific bits.
Notes:
• The installation of the hardware specified by this parameter
may require derating of drive output, or impose other
limitations. Refer to the hardware manual of the drive.
• This parameter cannot be changed while the drive is
running.
-
0000b…0111b Hardware options configuration word. 1 = 1
95.16 Router mode (Only visible with a BCU control unit)
Enables/disables router mode of the BCU control unit. When
router mode is active, the PSL2 channels connected to
another BCU (ie. those selected by 95.17 Router channel
config) are routed to the power units (converter modules)
connected to this BCU.
See section Router mode for BCU control unit (page 95).
Note: This parameter cannot be changed while the drive is
running.
Off
Off Router mode inactive. 0
On Router mode active. 1
Other [bit] Source selection (see Terms and abbreviations on page 114). -
No. Name/Value Description Def/FbEq16
Bit Name Information
0 EX motor 1 = The driven motor is an Ex motor provided by ABB for potentially
explosive atmospheres. This sets the required minimum switching
frequency for ABB Ex motors. Note: For non-ABB Ex motors,
contact your local ABB representative.
1 ABB sine filter 1 = An ABB sine filter is connected to the output of the drive/inverter.
2 High speed mode 1 = Minimum switching frequency limit adaptation to output
frequency active. This setting improves control performance at high
output frequencies (typically above 120 Hz).
3 Custom sine filter 1 = A custom sine filter is connected to the output of the
drive/inverter. See also parameters 97.01, 97.02, 99.18, 99.19.
4…15 Reserved