422 Parameters
96.11 User set save/load Enables the saving and restoring of up to four custom sets of
parameter settings. See section User parameter sets (page
91).
The set that was in use before powering down the drive is in
use after the next power-up.
Notes:
Hardware configuration settings such as I/O extension
module, fieldbus and encoder configuration parameters
(groups 14…16, 51…56, 58 and 92…93, and parameters
50.01 and 50.31), and forced input/output values (such as
10.03 and 10.04) are not included in user parameter sets.
Parameter changes made after loading a set are not
automatically stored – they must be saved using this
parameter.
If no sets have been saved, attempting to load a set will
create all sets from the currently active parameter settings.
Switching between sets is only possible with the drive
stopped.
No action
No action Load or save operation complete; normal operation. 0
User set I/O mode Load user parameter set using parameters 96.12 User set I/O
mode in1 and 96.13 User set I/O mode in2.
1
Load set 1 Load user parameter set 1. 2
Load set 2 Load user parameter set 2. 3
Load set 3 Load user parameter set 3. 4
Load set 4 Load user parameter set 4. 5
Save to set 1 Save user parameter set 1. 18
Save to set 2 Save user parameter set 2. 19
Save to set 3 Save user parameter set 3. 20
Save to set 4 Save user parameter set 4. 21
96.12 User set I/O mode
in1
When parameter 96.11 User set save/load is set to User set
I/O mode, selects the user parameter set together with
parameter 96.13 User set I/O mode in2 as follows:
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
No. Name/Value Description Def/FbEq16
Status of source
defined by par.
96.12
Status of source
defined by par.
96.13
User parameter
set selected
00Set 1
10Set 2
01Set 3
11Set 4