Fault tracing 537
FB14 Memory unit FW load
failed
The memory unit is empty, or
contains incompatible or
corrupted firmware.
Recycle the power to the control unit.
Check the sticker on the memory unit to
confirm that the firmware is compatible
with the control unit (ZCU-1x/BCU-x2).
Connect Drive composer PC tool
(version 2.3 or later) to the drive. Select
Tools - Recover drive.
If the problem persists, replace the
memory unit.
FF61 ID run Motor ID run was not
completed successfully.
Check the nominal motor values in
parameter group 99 Motor data.
Check that no external control system is
connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that the motor shaft is not locked.
Check the auxiliary code. The second
number of the code indicates the
problem (see actions for each code
below).
0001 Maximum current limit too low. Check settings of parameters 99.06
Motor nominal current and 30.17
Maximum current. Make sure that
30.17 > 99.06.
Check that the drive is dimensioned
correctly according to the motor.
0002 Maximum speed limit or
calculated field weakening
point too low.
Check settings of parameters
30.11 Minimum speed
30.12 Maximum speed
99.07 Motor nominal voltage
99.08 Motor nominal frequency
99.09 Motor nominal speed.
Make sure that
30.12 > (0.55 × 99.09) >
(0.50 × synchronous speed)
30.11 <
0, and
supply voltage >
(0.66 × 99.07).
0003 Maximum torque limit too low. Check settings of parameter 99.12 Motor
nominal torque, and the torque limits in
group 30 Limits.
Make sure that the maximum torque limit
in force is greater than 100%.
0004 Current measurement
calibration did not finish within
reasonable time.
Contact your local ABB representative.
0005…0008 Internal error. Contact your local ABB representative.
0009 (Asynchronous motors only)
Acceleration did not finish
within reasonable time.
Contact your local ABB representative.
000A (Asynchronous motors only)
Deceleration did not finish
within reasonable time.
Contact your local ABB representative.
Code
(hex)
Fault Cause What to do