Ratings 3-13AXD50000011888
Chapter 3
Ratings
3.1 Ratings
The ACS880+N5350 product line includes models to support each motor designed for cooling tower direct drive
applications. The following table provides the electrical ratings of each of the standard available models. If your need is for a
rating not listed below, contact your local ABB representative for support. (Symbols are described below the table.)
Table 3-1 Drive Ratings, Model Numbers and Frame Sizes with 50 and 60 Hz Supply
Catalog Number
ACS880-01-
Frame
Size
Input
Rating
Max
Current
Output Ratings
Light-Overload Use
I
1N
I
max
I
LD
P
LD
A A A kW hp
U
N
= 208…240V
24A3-2+N5350 R2 24.3 28.6 23.1 5.5 7.5
031A-2+N5350 R3 31 41 29.3 7.5 10
046A-2+N5350 R4 46 64 44 11 15
061A-2+N5350 R4 61 76 58 15 20
075A-2+N5350 R5 75 104 71 18.5 25
087A-2+N5350
R5
87 122 83 22 30
115A-2+N5350 R6 115 148 109 30 40
145A-2+N5350 R6 145 178 138 37 50
170A-2+N5350 R7 170 247 162 45 60
206A-2+N5350 R7 206 287 196 55 75
274A-2+N5350 R8 274 362 260 75 100
U
N
= 380…415V
12A6-3+N5350 R1 12.6 16 12 5.5 7.5
017A-3+N5350 R2 17 21 16 7.5 10
025A-3+N5350 R2 25 29 24 11 15
032A-3+N5350 R3 32 42 30 15 20
038A-3+N5350 R3 38 54 36 18.5 25
045A-3+N5350 R4 45 64 43 22 30
061A-3+N5350 R4 61 76 58 30 40
072A-3+N5350 R5 72 104 68 37 50
087A-3+N5350 R5 87 122 83 45 60
105A-3+N5350 R6 105 148 100 55 75
145A-3+N5350 R6 145 178 138 75 100
169A-3+N5350 R7 169 247 161 90 125
206A-3+N5350 R7 206 287 196 110 150
246A-3+N5350 R8 246 350 234 132 200
293A-3+N5350 R8 293 418 278 160 225
363A-3+N5350 R9 363 498 345 200 275
430A-3+N5350 R9 430 545 400 200 350