10.5 AW400 Memory Map
Increment: (figures between brackets ‘[x]’ indicate the number of similar variables repeated).
Char type: 1 byte
int type: 2 bytes
float type: 4 bytes
string type: 1 byte x string length
Type Hex addr. Name Description
int 0X0000 PgmMode Program mode (0-4) Transmitter, Washing, Regulator…
int 0X0002 Lng Language in use
char 0X0004 AccCode[6] Miro2Chem Password
char 0X000A TermAddr[4] Serial line address
int 0X000E SerSpeed Serial line speed
int 0X0010 SerType Serial line type
float 0X0012 Altitude Altitude where AW400 is mounted
int 0X0016 CCIinOR Set for CCI in OR mode
int 0X0018 Average Set for Average count
float 0X001A Delta Delta limit
float 0X001E pH_offset[3] Offset for PH (SPC), for 3 channels
float 0X002A P1[3] Calibration P1 value for 3 channels
float 0X0036 P2[3] Calibration P2 value for 3 channels
float 0X0042 P1U[3] User Calibration P1 value for 3 channels
float 0X00AE P2U[3] User Calibration P2 value for 3 channels
int 0X005A Light Set when back-light is ON
int 0X005C T_Units Temperature units
float 0X005E DefTemp Default temperature for termo-compensation
int 0X0062 AltUnits Altitude Units meters/feet
int 0X0064 Sigma Sigma enabled or not
float 0X0066 sK1 Sigma K1 parameter
float 0X006A sK2 Sigma K2 parameter
float 0X006E Hyst[3] Smoothing for each channel
int 0X007A wType Wash Type T17AU / T17SU
char 0X007C wT[4][9] Wash Timers T1-T4
float 0X00A0 Out_LO[3] Min. output value for 3 channels
float 0X00AC Out_HI[3] Max. output value for 3 channels
int 0X00B8 DacType[3] Type of DAC output
float 0X00BE AlLO[3] Alarms low level
float 0X00CA AlHI[3] Alarms high level
float 0X00D6 AlBA[3] Alarms Band
int 0X00E2 DO_AIR[3] Set when DO is in air
int 0X00E8 Reserved Reserved
0X0108 SerMode Type of RS485/422 serial line
int 0X0110A CIO 0 = No I/O Board, 1 = Yes I/O Board
char 0X0110C DoWash When set, TX has washing
char 0X0110D PidType Determine program PID mode
char 0X0110E Temp. Mode Ch. 2 When 0 use its own Temp. - When 1 uses Temp. Ch 1
char 0X0110F Temp. Mode Ch. 3 When 0 use its own Temp. - When 1 uses Temp. Ch 1
int 0X01110 Ena[3] Channels enabled
int 0X01116 Type[3] Channel types
float 0X0111C Chn_Val[3] Actual channel measurement
float 0X01128 Temperature[3] Actual channel temperature measurement
Table 14 - General Data Memory Map