ControlMaster CM10, CM15, CM30 and CM50
Universal process controllers and indicators,
1
/8,
1
/4 and
1
/2 DIN 4 Communication Level
IM/CM/C–EN 9
…Communication
RS485 Setup
Mode Selects the MODBUS serial communication serial link as 2 Wire, 4 Wire or Off – see Section 5.3,
page 15.
Baud Rate A selectable communication transfer rate up to 115.2 K baud (bits per second) maximum (default
19200 baud).
Parity Sets the parity bit (transmission error-checking) condition.
Selected from:
No Parity
Odd Parity
Even Parity
Tx Delay A set delay to the response from the transmitter in milliseconds. Maximum delay 100 ms.