92
3ADW000191R0500 DCS800 Quick guide edisf e
Signal
9.11
Diagnosis messages
Denition
EN
Diagnosemeldungen
Beschreibung
DE
Diagnosis messages
Descrizione
IT
Diagnosis messages
Denición
SP
Diagnosis messages
Description
FR
y = 0: only a single thyristor in bridge 2 is
not conducting (e.g. 3dd0020 means V22
is not conducting)
y = 1 … 6: additionally a second thyristor
in bridge 2 is no conducting (e.g. 3dd25
means V22 and V25 are not conducting)
dd = don’t care, the numbers of this digits
do not carry any information about the
thyristors of the second bridge.
Example: 36030: means V16 in bridge 1
and V23 in bridge 2 are not conducting
y = 0: nur ein einzelner Thyristor in
Brücke 2 leitet nicht (z.B. 3dd0020
bedeutet, dass V22 nicht leitet)
y = 1 … 6: darüber hinaus leitet ein
zweiter Thyristor in Brücke 2 nicht (z.B.
3dd25 bedeutet, dass V22 und V25 nicht
leiten)
dd = don’t care, diese Ziffern enthalten
keine Informationen über die Thyristoren
der ersten Brücke.
Beispiel:
36030: bedeutet, dass V16 in Brücke 1
und V23 in Brücke 2 nicht leiten
y = 0: un solo thyristor nel ponte 2 non
conduce (es. 3dd0020 significa che V22
non conduce)
y = 1…6: in aggiunta un secondo
thyristor nel ponte 2 non conduce (es.
3dd25 significa che V22 e V25 non
conducono)
dd = non considerare, i numeri di questi
digits non portano alcuna informazione
circa i thyristors del secondo ponte.
esempio: 36030: significa V16 nel ponte
1 e V23 nel ponte 2 non conducono
y = 0: solamente un tiristor del puente 2
ha cesado de conducir (p. ej. 3dd0020
significa que V22 ha dejado de conducir)
y = 1 … 6: adicionalmente, un segundo
tiristor del puente 2 ha cesado de
conducir (p. ej. 3dd25 significa que V22 y
V25 han dejado de conducir)
dd = carecen de importancia. Estos
números no aportan ninguna información
sobre los tiristores del segundo puente.
Ejemplo:
36030: significa que V16, en el puente 1,
y V23, en el puente 2, ya no conducen
y = 0 : seul un thyristor du pont 2 n’est
pas conducteur (par ex., 3dd0020 = V22
non conducteur)
y = 1 … 6 : un second thyristor du pont
2 n’est pas conducteur (par ex., 3dd25 =
V22 et V25 non conducteurs)
dd = sans importance, ces chiffres ne
contiennent aucune information sur les
thyristors du second pont.
Exemple :
36030= V16 (pont 1) et V23 (pont 2) non
conducteurs
A124 SpeedScale (alarm speed
scaling):
A124 SpeedScale (Alarm
Drehzahlnormierung):
A124 SpeedScale (allarme scalatura
velocità):
A124 SpeedScale (alarma del escalado
de velocidad):
A124 ErrFormatVit (alarme échelle de
vitesse):
40000
49999
the parameter with the speed scaling
conflict can be identified by means of the
last 4 digits
der Parameter mit dem Konflikt in der
Drehzahlnormierung kann anhand der
letzten vier Ziffern ermittelt werden
Il parametro con conflitto scalatura
velocità può essere identificato per
mezzo degli ultimi 4 digits
el parámetro que presenta el conflicto
de escalado de velocidad puede
identificarse mediante sus últiimas cuatro
cifras
le paramètre à l’origine du conflit est
identifié par les 4 derniers chiffres.
F549 ParComp (fault parameter
compatibility conflict):
F549 ParComp (Fehler Parameter
Kompatibilität):
F549 ParComp (guasto per
incompatibilità parametro):
F549 ParComp (fallo de conflicto de
compatibilidad de parámetros):
F549 CompatibPara (défaut conflit
compatibilité paramètres):
50000
59999
the parameter with the compatibility
conflict can be identified by means of the
last 4 digits
der Parameter mit dem
Kompatibilitätskonflikt kann anhand der
letzten vier Ziffern ermittelt werden
il parametro con conflitti di compatibilità
può essere identificato per mezzo degli
ultimi 4 digit
el parámetro que presenta el conflicto
de compatibilidad puede identificarse
mediante sus últimas cuatro cifras
le paramètre à l’origine du conflit est
identifié par les 4 derniers chiffres.
F545 ApplLoadFail (ControlBuilder
DCS800 application programming):
F545 ApplLoadFail (ControlBuilder
DCS800 Applikationsprogrammierung):
F545 ApplLoadFail (programma
applicativo Control Builder DCS800):
F545 ApplLoadFail (programación
de aplicaciones para el DCS800 con
ControlBuilder):
F545 DéfChargAppl (programme
d’application ControlBuilder DCS800):
64110
task not configured Zykluszeit nicht konfiguriert task non configurata tarea no configurada che non configurée
64112
attempt to run an illegal copy of a
protected program
Versuch, eine illegale Kopie eines
geschützten Programms auszuführen
tentativo di attivare una copia illegale di
un programma protetto
se ha intentado ejecutar una copia ilegal
de un programa protegido
tentative d’exécution d’une copie interdite
d’un programme protégé
64113
retain data invalid caused by SDCS-
CON-4 hardware problem
gesicherte Daten auf der SDCS-CON-4
sind durch ein Hardwareproblem ungültig
dati non validi trattenuti a causa di
problema ardware della SDCS-CON-4
se conservan los datos no válidos
causados por el problema de hardware
de SDCS-CON-4
copie de données erronée en raison d’un
problème matériel de la carte SDCS-
CON-4
64125
5 ms task halted (e.g. task contains an
endless loop)
5 ms Zykluszeit angehalten (z.B.
Zykluszeit enthält eine Endlosschleife)
task 5 ms bloccata (es. la task contiene
un endless loop)
tarea de 5 ms detenida (p. ej. la tarea
contiene un bucle infinito)
tâche arrêtée pendant 5 ms (ex., la tâche
comporte une boucle infinie)
64126
20 ms task halted (e.g. task contains an
endless loop)
20 ms Zykluszeit angehalten (z.B.
Zykluszeit enthält eine Endlosschleife)
task 20 ms bloccata (es. la task contiene
un endless loop)
tarea de 20 ms detenida (p. ej. la tarea
contiene un bucle infinito)
tâche arrêtée pendant 20 ms (ex., la
tâche comporte une boucle infinie)
64127
100 ms task halted (e.g. task contains an
endless loop)
100 ms Zykluszeit angehalten (z.B.
Zykluszeit enthält eine Endlosschleife)
task 100 ms bloccata (es. la task
contiene un endless loop)
tarea de 100 ms detenida (p. ej. la tarea
contiene un bucle infinito)
tâche arrêtée pendant 100 ms (ex., la
tâche comporte une boucle infinie)
64128
500 ms task halted (e.g. task contains an
endless loop)
500 ms Zykluszeit angehalten (z.B.
Zykluszeit enthält eine Endlosschleife)
task 500 ms bloccata (es. la task
contiene un endless loop)
tarea de 500 ms detenida (p. ej. la tarea
contiene un bucle infinito)
tâche arrêtée pendant 500 ms (ex., la
tâche comporte une boucle infinie)