5.3 UPS and battery location
The minimum clearances needed to allow proper airflow around the UPS, and to allow proper service
and maintenance, must be observed. They are detailed below:
Fig 5.3-1: UPS and battery location (Clearances)
ST40, ST60, ST80, ST120 ST200
UPS + battery
cabinets in row.
Back clearance for ventilation
(forced air outlet)
200 mm 300 mm
Front clearance needed to
allow a correct door opening
1000 mm
Maximum door opening
angle
115°
(Top clearance is only needed if
there is no side clearance)
400 mm