FSM4000 ELECTROMAGNETIC FLOWMETER |  DS/FSM4000-EN REV. L 
 
 
 
— 
… Transmitter 
 
 
 
DN 3 to DN 1000 (¹⁄₁₀ to 40”) with PROFIBUS PA / FOUNDATION Fieldbus 
 
 
S4 transmitter (wall mount housing) 
 
  Functional ground (busbar) 
  Switch output (see the section ‘Connection examples for peripherals’ 
in the operating instruction and/or on the data sheet) 
  Digital communication 
A PROFIBUS PA design conforming to IEC 61158-2 (Profile 3.0) 
3a:  U = 9 to 32 V, I = 10 mA (normal operation) 
3a:  U = 9 to 32 V, I = 13 mA (in the event of error/FDE) 
3a:  Terminals: 97/98, PA+/PA- 
3a:  (see the chapter ‘Connecting via M12 plug’ in the operating 
3a:  instruction and/or on the data sheet) 
B FOUNDATION Fieldbus design conforming to IEC 61158-2 
3a:  U = 9 to 32 V, I = 10 mA (normal operation) 
3a:  U = 9 to 32 V, I = 13 mA (in the event of error/FDE) 
3a:  Terminals: 97/98, FF+/FF- 
3a:  (see the chapter ‘Connecting via M12 plug’ in the operating 
3a:  instruction and/or on the data sheet) 
C Bus termination with installed bus termination 
3a:  components with hook switches closed 
  Magnetic coil cable: 
shielded 2 x 1 mm2 CE type 227 TEC 74 
  ABB order no. D173D147U01, 10 m included in shipment, standard 
 
  Power supply 
Low voltage: 100 to 230 V AC, terminals L, N,   
Extra-low voltage: 20.4 ...26.4 V AC;  
Extra-low voltage: 20.4 to 31.2 V DC 
Extra-low voltage: Terminals 1+, 2-,   
Frequency: 47 Hz ≤ f ≤ 53 Hz; 50 Hz power supply 
Frequency: 56 Hz ≤ f ≤ 64 Hz; 60 Hz power supply 
  Shielded signal cable:  
Power supply for flowmeter sensor with preamplifier 
Terminals U+, U- instead of 2S and 1S in standard unit 
  Steel shielding 
  Aluminum foil 
  Yellow 
  Shield 
  Blue 
  Red 
  White 
  Shielded signal cable: ABB order no. D173D025U01, 
10 m, included in shipment 
  Without preamplifier  
 
With preamplifier (always at DN 1 to DN 8 [¹⁄₁₀ to ⁵⁄₁₆”]) 
Figure 37:  Electrical connection transmitter S4 with PROFIBUS PA / FOUNDATION Fieldbus 
 
Note 
•  We recommend that shielded output cables be used with the shields connected to the functional ground at one end. 
•  If the sensor is equipped with a preamplifier for low conductivity or in nominal diameter range of DN 1 to DN 8 (¹⁄₁₀ to ⁵⁄₁₆”), 
the shieldings of the signal wires must be connected to terminals U+ and U− on both the sensor and the transmitter.