EasyManua.ls Logo

ABB IM300-I - Page 41

ABB IM300-I
109 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM300 Intelligent Power Monitoring Instrument
39
Fig 3-3-13 Backlight time
settings page
Fig 3-3-14 Statistical interval of
electric parameter maximum/minimum
value settings
Fig 3-3-15 Over current alarm parameter
settings page
indicates 50Hz
±range
15
Related PF
Unidirectional /
Bidirectional
30
Related Sc
Unidirectional
Screen 10
:
Back-light time settings
This page is used to set the backlight lighting time. The
upper display shows the word "Ld-T", indicates that the
current page as the backlight time setting page, as shown in
fig. 3-3-13.
Backlight time range is from 0 to 30 minutes, when set
to 0, the backlight is on.
Screen 11: Statistical interval of electric parameter
maximum/minimum value settings
“S—T” on the top of the screen denotes the statistical
interval of electric parameter maximum/minimum value
settings page. as shown in fig 3-3-14: The range of
maximum or minimum statistics interval is from 1
minute to 1440 minutes.
Screen 12:Over current alarm parameter settings.
.The word "w-oc" is displayed at the top of the
screen, indicating that the current page is over current
alarm parameter settings page.
The permitted range of the alarm is 0~1. 0 indicates
that the alarm is not allowed, and 1 indicates that the
alarm is allowed.
The limit value and return value range from 0 to 6000A; the delay time
range from 1 to 60000 ms.