3.9.4 Battery monitoring
Table 11 lists Modbus commands to monitor the energy storage system operated by the PQstorI. These
function are detailed further in Section 3.7.3.
—
NOTE: For grid code related parameters, please refer to the PQstorI Grid Code Functionality Manual
and PQstorI Modbus table.
3.9.5 PQstorI commands
Table 12 lists Modbus commands to operate the PQstorI. These functions are described in further detail
in Section 3.5.5.
—
Table 11: Modbus commands to monitor the state of the battery
—
Table 12: Modbus commands for operating the PQstorI
Name Address Unit Type Register
length
Range Description
Min. Max.
Battery
Voltage
V Float DC voltage (V) on DC output of
Battery
Current
A Float DC current (A) on DC output of one
positive when discharging
the battery
Udc (Inverter
DC voltage)
V Float The DC voltage present on
the inverter DC bus
Name Address Unit Type Register
length
Range Description
Min. Max.
Start request - Word
provided no error is
currently present
Stop request - Word
prevent if from restarting as soon
as the error has disappeared
Reset fault - Word
fault that has caused the unit stop
Set P kW Float Active power (kW) to be
injected into the grid (when in
current source mode). Positive
target means discharging
Set Q kvar Float Reactive power (kvar) to be
injected into the grid
(when positive, inverter
behaves like a capacitor)
Heart beat
timeout
- Word Heart beat signal: Once modbus
client has set it to non-zero value,
at least otherwise the inverter
will stop and generate a
heartbeat fault. By default
heartbeat is not active