3.1.6 Type designation
Table 1 Type designation (See Figure 9.)
Designation
(i.e. PSTX370-600-70)
Desription
PSTX Softstarter type
370 Current rating
370 = 370A
600 Main voltage
600 = 208 - 600V 50/60 Hz
690 = 400 - 690V 50/60 Hz
70 Supply Voltage
70 = 100 - 250V 50/60 Hz
3.1.7 Environmental influence
The product is designed to minimize the environmental
affects during manufacturing and use of the product.
Most of the materials used are recyclable and shall be
handled and recycled according to local laws.
Further information reg
arding used material and
recycling of the product
can be found at ABB Website.
PSTX-370-600-70
Supply Voltage
70 = 100 - 250V 50/60 Hz
Main voltage
600 = 208 - 600V 50/60 Hz
690 = 400 - 690V 50/60 Hz
Current rating
370 = 370A
Softstarter range
9
1SFC132081M0201
Figure. 9: Type designation
3.1.8 Specifications
Table 2 Specifications
General data Description
Degree of protection:
Main circuit
PSTX30-105: IP10 PSTX142-370: IP00
Degree of protection:
Supply and control
circuit
PSTX30-105: IP20 PSTX142-370: IP20
Operating position Vertical at ± 30°
Ambient temperature Storage: -40 °C to +70 °C
(-104 °F to 140 °F)
Operation: -25 °C to +60 °C
(-77°F to 104 °F)
De-rating: + 40 °C to + 60 °C
(104° F to 140° F) with derating 0,6%/1° C
(0,33%/1grF)
Altitude 1000 m (3281 ft.) above sea level without
derating. 1000 - 4000 m (3281 - 13123 ft.)
with derating 0,7%/100 m (0,22%/100ft)
Pollution degree 3
Relative humidity 5 - 95% (non condensing)
Standards IEC 60529
IEC 60947-1
IEC60947-4-2
Standards UL UL508
PTC input IEC 60947-8 Mark A detectors
DIN 44081 and DIN 44082
EMC
IEC 60947-4-2 Class A
1
Marine approvals Contact your ABB sales office
1
The softstarter is designed for class A equipment.
Use of the product in domestic environments can cause
radio interference. If so, it can be necessary to use more
mitigation procedures.