- 65 -
000411AG
7 - Operation
During the grid voltage check and measurement of the insulation re-
sistance, the values for the grid voltage and frequency and the insula-
tion resistance measured by the inverter are shown on the display. The
inverter completes parallel connection with the grid SOLELY if the grid
parameters meet the ranges provided for by the regulations in force and
if the insulation resistance is greater than 1Mohm.
If the preliminary checks for parallel connection to the grid are suc-
cessful, the inverter connects to the grid and begins to export power to
the grid. At this stage, the display shows the inverter’s parameters in
cycles. The green LED stays lit whereas the others are off.
The “Nation” value (grid standard) that can be selected are listed in the
following table:
Displayed name Display language
No Nation English
AS4777 English
Brazil English
C10-11 100% French
C10-11 110% French
CEI021 EXT
[1]
Italian
CEI021 INT
[1]
Italian
Corsica French
Czech Czech
EN50438 English
France 14 French
Greece English
Hungary English
Ireland English
Israel English
Korea English
Netherl. Dutch
Portugal English
RD 1699 Spanish
Romania English
Slovenia English
S.Africa English
Taiwan English
Turkey LV English
UKG59 English
UKG83 English
THAIL. MEA. English
THAIL. PEA. English
VDE 0126 English
VDE 4105
[2]
German
[1] Select the “CEI021 INT” Nation if you wish to use the interface protections integrated in the inverter for sy-
stems with a power lower than 6kW; Select “CEI021 EXT” if the inverter is connected to a system with a power
greater than 6kW or if you wish to use external interface protections for systems with a power lower than 6kW.
[2] Invalid nation for models PVI-5000/6000-TL-OUTD installed in Germany
The list of grid standards given in the table was valid at the time of issue of the manual. It will
be continually updated as new country standards with which the inverter is compatible are
introduced